Our Projects

Sheet Metal Connectors Inc. supplied all the duct work for the new Minnesota Twins ballpark Target Field.
Double Wall Rectangular Duct and Fittings Specs
Sheet Metal Connectors, Inc. double wall rectangular duct and
fittings are one part of our complete line of HVAC products. Double wall
rectangular duct is constructed with TDC end treatments.
There are two different types of applications:
- • Acoustical double wall duct for noise control
- • Thermal double wall duct for temperature control
Straight double wall duct comes standard with stiffening beads.
Double wall duct is fabricated with either Snap Lock or Pittsburgh
longitudinal seams. Sealant is available in the seams upon request.
Double wall duct is manufactured completely assembled with TDC corners
installed. All sizes shall be listed using inside dimensions.
Acoustical Double Wall
Standard acoustical double wall is for noise control.
Constructed of a perforated inner shell surrounded by a layer of
insulation and covered by a solid outer shell. The perforated inner
shell has 3/32” diameter holes staggered at 3/16” on center for a clear open area of 23%.
Thermal Double Wall
Standard thermal double wall is for temperature control.
Constructed of a solid shell surrounded by a layer of insulation and
covered by a solid outer shell.
Fittings
Sheet Metal Connectors, Inc. manufactures double wall fittings
in most sizes and configurations. Double wall fittings are manufactured
on our state of the art fabrication equipment. All double wall fittings
are fabricated with stiffening beads on duct sizes 19” wide and larger
which have more than 10 square feet of unbraced panel. This requirement
is applicable to 20 gauge or less in thickness and 3” W.G. or less. Most
double wall fittings are fabricated with Pittsburgh seams. Double wall
fittings are completely assembled with all accessories (TDC corners,
vane & rail, etc...) installed.
Turning Vane and Rail
SMC manufactures several types of turning vane and E-Z rail.
Turning vane and E-Z rail are recommended for square throat elbows and
tees. When using turning vane and E-Z rail performance is greatly
enhanced in the HVAC duct system. Test data is available upon request.
Maximum Unsupported Vane Length
- 4” single turning vane ......36” max. length
- 2” double turning vane .....48” max. length
- 4” double turning vane .....72” max. length
- 4” acoustical vane ...........72” max.length
- When exceeding maximum vane length, vanes can be
installed in sections or a tie rod can be tack welded to the face of the
turning vane.
Transverse Joint and Intermediate Reinforcement
SMC manufactures many different types of reinforcement. SMC’s
most popular types are as follows:
- Tie Rod Reinforcement: threaded inserts installed into each
end of thin wall (emt) conduit. These are installed internally atboth
the joint and/or intermediate duct spacing. - R-Angle Reinforcement: roll formed pre-punched angle iron
reinforcement. See chart below.

Insulation
Sheet Metal Connectors, Inc. double wall rectangular duct is a
dependable, erosion resistant alternative to lined rectangular duct,
providing improved protection for insulation exposed to the airstream.
In double wall rectangular duct a metal inner liner insures that high
airflow velocities cannot separate insulation by pulling away from the
duct's outer wall and creating erosion or airflow problems.
Duct liner shall be of the specified materials, thickness, and
density of the contractors request. All sizes shall be listed using
inside dimensions. Each layer of duct liner shall be attached with a
minimum of 90% coverage of adhesive at the liner contact surface area.
SMC constructs each piece with an inner shell (perforated or
solid) surrounded by a layer of insulation and covered by a solid outer
shell. The insulation is used in both acoustical and thermal duct
systems.
SMC solves air quality problems caused by bacteria and other
contaminants that can embed in fibrous materials. These air quality
problems can be a health hazard in environments such as schools,
hospitals, laboratories, and food or pharmaceutical plants. In cases
where additional erosion or contamination protection is desired for such
an environment, we can provide a customer specified barrier material
(mylar) between the insulation and the perforated liner.
Standard insulation is 1" thick with 1 1/2 lb. per cubic foot
density. See chart below for specifications. Many other thickness'
and densities are available, consult factory.


Specification Compliance
SMC standard insulation meets the requirements of the following
codes and specifications:
NFPA 90A and NFPA 90B
NAIMA Standard AHC-101
ASTM C 1071 Type 1 Replaces HH-I-545B Type 1
Note:
SMACNA Testing and Research Institute verified that Sheet Metal
Connectors, Inc. shop standards comply with the 1995-2nd edition of the
SMACNA HVAC Duct Construction Standards.